SPECIFICATIONS (CONTINUED)
selected to that group. Doors can be removed from the assigned group by re-selecting them,
while in the group define mode, which will toggle the blue outline around the door icon to the off
state.
l. Isolate - Any door shall be configured to be isolated. Isolating a door keeps that door from being
unlocked. Isolate doors, have a Yellow “X” on the icon. Any isolation or removal of isolation
for a door shall be recorded to the Reporter/Logger.
m. Shunt Any door shall have the ability to be shunted. Shunting a door prevents the door from
causing a breach alarm when opened in a means other than through the PLC. Selecting the Shunt
function button will cause a flashing green outline to appear around door candidates. Selecting a
door to shunt will cause the flashing green outline to become steady around the door icon.
n. Interlocks - Where two or more doors with electric hardware form a sallyport or where interlocks
between hardware sets are indicated on the plans or specs, or will be specified by Harris County
or engineer at the time of graphic panel submissions, the operation of the individual hardware sets
shall be as follows: The controls will allow only one of the hardware sets to be in the non-
secured condition at any given time unless the interlock override function is activated. These
doors shall be indicated on the screen with a yellow outline around the door icon. The officer
must press the interlock override pushbutton prior to unlocking a door to defeat the interlock.
Logic shall also be incorporated such that the interlocks cannot be defeated by pressing two door
pushbuttons simultaneously on the graphic panel or touchscreen.
2. Communications Control - Communications control shall be integrated with the touchscreen controls
to operate in the following manner. Each touchscreen shall have its own dedicated intercom
amplifier. Systems that share a common intercom amplifier and/or intercom buss and show BUSY,
when in use, will not be accepted.
a. Intercom Communications - Communicating to an intercom staff station location from a control
location shall cause a PLC output to energize a sound card relay and connects the talk-back
amplifier to the sound card's audio bus while also placing the control station's audio speaker onto
the talk-back amplifier's speaker output. The control location then automatically monitors the
intercom location. When the control officer presses push to talk, then the intercom staff station
speaker shall be able to hear the control officer. Control stations shall be able to call other control
stations utilizing the existing talk back amplifier configuration.
b.. Paging - Page zone selection shall be configurable. Each intercom staff station shall be
configurable to be included in any paging zone. The system shall have the ability to monitor
paging speakers as well as staff stations.
c. Isolate - Any intercom staff station can be configured to be isolated in software. When the
pushbutton on an isolated staff station is pressed, then the audible annunciation at the officer's
control station shall automatically be suppressed for that station. Visual annunciation, though,
shall occur at the officer's control station. Isolate intercom stations shall have a yellow “X” on
the intercom icon.
d. Spot/Assessment Monitor - When communications are established with a staff station, the camera
in the area around the staff station shall be displayed on the Spot/Assessment Monitor. When
communications are terminated, the Spot/Assessment Monitor will display the last camera
viewed. The cameras that are displayed shall be configurable for each alarm.
3. Video Control - Video control shall be integrated with the touchscreen controls to operate as an
integrated HMI system.